How to Replace Flange Gaskets for Gate Valves
Release time:
Aug 03,2024
How to Replace Flange Gaskets for Gate Valves
一、Preparation
1、Materials: butter, cotton gauze, leakage detection fluid, sealing gasket.
2、Tools: spanners, screw spinners.
二、The operation steps
1、Remove the flange connection bolts, remove the valve or remove the leakage end pipe. Remove the used gasket on the sealing surface.
2、Select the appropriate gasket, and evenly apply a layer of butter on both sides.
3、Place the sealing gasket on the sealing surface between the two flanges, align the centre of the two flanges and the centre of the bolt holes, load the bolts, screw on the nuts, and tighten the nuts diagonally with even force for several times. The bolt extends the length of the nut 2 to 3 pitches is appropriate. Flange gasket installation is completed, should be done after the working pressure test pressure without leakage is qualified.
四、 Gasket installation of five points
1、Selected right: flange, bolt, gasket form, material, size should be based on the operating conditions and the structural form of the flange face selection of appropriate.
2、Check the fine: before installation should be carefully check the flange, bolts, nuts, gaskets quality, there should be no burrs, unevenness, cracks, and other defects. Carefully check the flange, pipe installation, there should be no partial mouth, wrong mouth, wrong hole and other phenomena.
3、Wash the clean: flange sealing surface must be cleaned, bolts, gaskets shall not be sticky impurities, oil, etc.
4、Loaded with the right: gaskets should be concentric with the pipe or pipe fittings.
5、On the even: the installation of bolts, nuts should be uniform force, tighten symmetrically in several times.