Common Problems

One-stop Solution for Valve Products

Why does not the steam trap drain ?


Release time:

Jun 17,2024

The steam Trap is a key component for controlling the discharge of condensate and water vapor from piping systems. Its main function is to provide a discharge port on the piping system to discharge the condensate from the water vapor to ensure smooth piping and prevent system failure. Non-drainage is one of the most common problems with the steam trap.

Reasons for non-drainage:

1. Steam pressure is too low;

2. Steam and condensate are not entering the trap;

3. The float of the free float type steam trap is too light;

4. The valve stem of the free float type steam trap is jammed against the valve sleeve;

5、The valve hole or channel is blocked;

6. The plate of the thermostatic trap breaks off, blocking the valve hole.

Repair Methods:

1、 Adjust the steam pressure;

2,、Check whether the valve on the steam pipe is closed or blocked;

3、Accentuate the weight of the float or replace the float;

4、Overhaul or replace the valve stem and valve sleeve to make them flexible;

5. Remove clogging debris and install a strainer in front of the trap;

6、Replace the valve spool.